  gas generator set GS200-6S 200 kwe / 60 hz / standby 208 - 600v (reference gp175n6s for prime rating technical data) system ratings standby (ng) gs200n6sga gs200n6sda gs200n6spa gs200n6sja gs200n6sra gs200n6sna standby (lp) gs200l6sga gs200l6sda gs200l6spa gs200l6sja gs200l6sra gs200l6sna voltage (l-l) 240v** 240v** 208v** 240v** 480v** 600v** phase 1 1 3 3 3 3 pf 1.0 1.0 0.8 0.8 0.8 0.8 hz 60 60 60 60 60 60 natural gas ratings: amps 750 750 694 601 300 240 natural gas ratings: kw/kva 180/180 180/180 200/250 200/250 200/250 200/250 lp gas ratings: amps 541 541 451 390 195 156 lp gas ratings: kw/kva 130/130 130/130 130/162 130/162 130/162 130/162 skva@30% voltage dip 425 370 608 608 809 720 generator model* 433csl6216 432psl6228 432csl6210 432csl6210 432csl6210 432psl6246 temp rise 130 c/40 c 130 c/40 c 130 c/40 c 130 c/40 c 130 c/40 c 130 c/40 c connection 12 lead zig-zag 4 lead 12 lead low wye 12 lead hi delta 12 lead hi wye 4 lead wye * consult the factory for alternate con guration. ** ul 2200 o ? ered // ? generator set is designed and manufactured in facilities certi ed to standards iso 9001:2008 and iso 14001:2004 // ? ul 2200 / csa ? optional ? ul 2200 listed ? csa certi ed // ? performance assurance certification (pac) - generator set tested to iso 8528-5 for transient response - veri ed product design, quality and performance integrity - all engine systems are prototype and factory tested // ? power rating - accepts rated load in one step per nfpa 110 certifications and standards
2 // / ? / GS200-6S * represents standard product only. consult factory/mtu onsite energy distributor for additional con gurations. // ? engine air cleaner oil pump oil drain extension & s/o valve full flow oil filter jacket water pump thermostats blower fan & fan drive radiator - unit mounted electric starting motor - 24v governor ? electronic isochronous base - formed steel sae flywheel & bell housing charging alternator - 24v battery box & cables flexible fuel connectors flexible exhaust connection epa certi ed engine // ? generator nema mg1, ieee and ansi standards compliance for temperature rise and motor starting self ventilated and drip-proof superior voltage waveform solid state, volts-per-hertz regulator 1% voltage regulation no load to full load brushless alternator with brushless pilot exciter 4 pole, rotating field 130 c maximum standby temperature rise 1 bearing, sealed flexible coupling full amortisseur windings 125% rotor balancing 3-phase voltage sensing 100% of rated load - one step 5% maximum total harmonic distortion // ? digital control panel(s) digital metering engine parameters generator protection functions engine protection sae j1939 engine ecu communications windows ? -based software multilingual capability remote communications to rdp-110 remote annunciator 16 programmable contact inputs up to 11 contact outputs ul recognized, csa certi ed, ce approved event recording ip 54 front panel rating with integrated gasket nfpa110 compatible standard equipment* // ? mtu onsite energy is a single source supplier // ? global product support // ? 2 year standard warranty // ? 11.1 l turbo engine charge air cooling - 11.1 liter displacement - 4-cycle // ? 3-way catalyst // ? optional fuels: lp liquid and dual fuel // ? engine-generator resilient mounted // ? complete range of accessories // ? generator - brushless, rotating field generator - 2/3 pitch windings - 300% short circuit capability with optional pmg // ? digital control panel(s) - ul recognized, csa certi ed, nfpa 110 - complete system metering - lcd display // ? cooling system - integral set-mounted - engine driven fan standard features*
3 // / ? / GS200-6S // ? engine manufacturer doosan model 11.1l cac type 4-cycle arrangement 6-inline displacement: l (in 3 ) 11.1 (673) bore: cm (in) 12.3 (4.84) stroke: cm (in) 15.5 (6.1) compression ratio 10.5:1 rated rpm 1,800 engine governor bosch maximum power (ng): kwm (bhp) 225 (302) maximum power (lp): kwm (bhp) 155 (208) speed regulation 0.5% air cleaner dry // ? liquid capacity (lubrication) total oil system: l (gal) 28.5 (8) engine jacket water capacity: l (gal) 25 (5.5) system coolant capacity: l (gal) 149 (32.8) // ? electrical electric volts dc 24 cold cranking amps under -17.8 c (0 f) 1,050 // ? fuel inlet fuel supply connection size 2? npt fuel supply pressure: mm h 2 0 (in. h 2 0) 178?279 (7?11) // ? fuel consumption (ng-1000 btu/ft 3 / lp-2500 btu/ft 3 ) ng lpg at 100% of power rating: m 3 /hr (ft 3 /hr) 59.9 (2,115) 19.9 (704) at 75% of power rating: m 3 /hr (ft 3 /hr) 46.7 (1,648) 17 (600) at 50% of power rating: m 3 /hr (ft 3 /hr) 32.8 (1,157) 11.5 (404) // ? cooling - radiator system ambient capacity of radiator: c (f) 50 (122)* maximum restriction of cooling air, intake, and discharge side of rad.: kpa (in. h 2 0) 0.12 (0.5) water pump capacity: l/min (gpm) 310 (82) heat rejection to coolant: kw (btum) 194.6 (11,071) heat radiated to ambient: kw (btum) 40.4 (2,295) fan power: kw (hp) 10.4 (13.9) 10.4 (13.9) * installation of enclosures reduces the ambient capacity of the cooling system by 1 c (1.8 f). gravity exhaust louvers reduce ambient capacity of the cooling system by an additional 3 c (5.5 f). // ? air requirements aspirating: *m 3 /min (scfm) 11.7 (400) air flow required for rad. cooled unit: **m 3 /min (scfm) 63 1 (22,300) remote cooled applications; air flow required for dissipation of radiated gen-set heat for a max of 25 f rise: *m 3 /min (scfm) 237 (8,365) * air density = 1.184 kg/m 3 (0.0739 lbm/ft 3 ) ** at 0.25 kpa (1 in. h 2 0) static pressure and 52 c (125 f) at radiator // ? exhaust system gas temp. (stack): c (f) 694 (1,281) gas volume at stack temp: m 3 /min (cfm) 38.8 (1,371) maximum allowable back pressure: kpa (in. h 2 0) 2.5 (10.25) application data
4 // / ? / GS200-6S weights and dimensions ? mtu onsite energy. subject to alteration due to technological advances. oe 23 470 (72 3e) 2014-01 materials and speci cations subject to change without notice. c/f = consult factory/mtu onsite energy distributor emissions data fuel type thc + no x co natural gas 2.24 0.26 liquid propane 0.08 0.25 all units are in g/hp-hr and are epa d2 cycle values. rating definitions and conditions // ? ambient capability factor at 984 ft (300 m). consult your local mtu onsite energy power generation distributor for other altitudes. // ? standby ratings apply to installations served by a reliable utility source. the standby rating is applicable to varying loads for the duration of a power outage. no overload capability for this rating. ratings are in accordance with iso 3046-1, bs 5514, as 2789, and din 6271. // ? deration factor: production tolerances in engines and installed components can account for power variations of 5%. altitude, tempera- ture and excessive exhaust and intake restrictions should be applied to power calculations. consult your local mtu onsite energy power generation distributor for derations. drawing above for illustration purposes only, based on standard open power 480 volt generator set. lengths may vary with other voltages. do not use for installation design. see website for unit speci c template drawings. sound data is provided at 7 m (23 ft). generator set tested in accordance with iso 8528-10 and with in nite exhaust. system dimensions (l x w x h) weight (dry) open power unit (opu) 3,607 x 1,591 x 2,026 mm (142 x 62.6 x 79.75 in) 3,096 kg (6,258 lb) weights and dimensions are based on open power units and are estimates only. consult the factory for accurate weights and dimen sions for your speci c generator set. sound data unit type standby full load (ng) standby full load (lp) level 0: open power unit db(a) 86.3 86.1 mtu onsite energy a rolls-royce power systems brand www.mtuonsiteenergy.com


▲Up To Search▲   

 
Price & Availability of GS200-6S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X